@V4ler1an - Your suspicions about how your system was installed are correct - it's really rare to have boilers installed with hot water diverter kits here. In any event, I think this video might help you: https://www.youtube.com/watch?v=RJCGOtDLuNQ.
from ems-esp32.
that's like a 2 second change. I'll do it ASAP
in the meantime, you can override it using Customizations
from ems-esp32.
in dev11. Max is 45
from ems-esp32.
Brilliant, thank you.
from ems-esp32.
Ah... a problem. It seems the boiler's weather comp settings also limits the value to 30. My automation no longer errors but the boiler puts it back to 30. Is there any way around that do you think?
from ems-esp32.
hmm, not sure. is it similar to https://emsesp.github.io/docs/Troubleshooting/#changing-a-value-works-at-first-but-is-then-reset-to-its-original-value ?
from ems-esp32.
The summer temp setting on the boiler is digital through menus, not a dial (if that's in any way relevant, after reading through the link you sent). Here's a quick syslog trace when i attempt to set it to 40. Anything revealing on the behaviour?
2024-05-18 14:14:24.163 I 11: [command] Calling command 'boiler/summertemp' (summer temperature) with value 40
2024-05-18 14:14:24.230 T 12: [emsesp] Me(0x0B) -W-> boiler(0x08), WeatherComp(0x28), data: 28 (offset 3)
2024-05-18 14:14:24.253 T 13: [emsesp] boiler(0x08) -B-> All(0x00), WeatherComp(0x28), data: 1E (offset 3)
2024-05-18 14:14:26.475 T 14: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorFastPlus(0xE4), data: 10 20 2D 2D 00 CB 00 01 0E 00 00 00 06 01 27 00 00 80 00 00 00 0D 00 01 0E 00 00
2024-05-18 14:14:26.652 T 15: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorFastPlus(0xE4), data: 00 00 00 00 EE 00 00 (offset 35)
2024-05-18 14:14:26.844 T 16: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorSlowPlus2(0xE3), data: 04 00 00 00 00 00 00 00 00 00 00 01 0E 00 64 46 00 00 00 00
2024-05-18 14:14:27.087 T 17: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorWWPlus(0xE9), data: 05 80 00 80 00 00 00 00 00 46 3C 00 00 02 00 00 00 00 00 00 00 00 00 05 02 00
2024-05-18 14:14:36.485 T 18: [emsesp] boiler(0x08) -B-> All(0x00), UBADevices(0x07), data: 0B 00 00 00 00 00 00 00 00 00 00 00 00 00 00
2024-05-18 14:14:36.656 T 19: [emsesp] boiler(0x08) -B-> All(0x00), UBAOutdoorTemp(0xD1), data: 00 BC
2024-05-18 14:14:37.203 T 22: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorSlowPlus(0xE5), data: 01 00 40 00 00 73 00 00 20 00 00 39 E2 02 9E 53 00 00 00 02 9E 53 00 39 E2 00 64
2024-05-18 14:14:37.376 T 23: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorSlowPlus(0xE5), data: 00 00 00 00 (offset 28)
2024-05-18 14:14:37.601 T 24: [emsesp] boiler(0x08) -B-> All(0x00), ?(0x02D6), data: 00 00 00 00 00 46 00
2024-05-18 14:14:37.799 T 25: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorFastPlus(0xE4), data: 10 20 2D 2D 00 CB 00 01 0E 00 00 00 06 01 27 00 00 80 00 00 00 0D 00 01 0E 00 00
2024-05-18 14:14:46.493 T 29: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorFastPlus(0xE4), data: 10 20 2D 2D 00 CB 00 01 0E 00 00 00 06 01 27 00 00 80 00 00 00 0D 00 01 0E 00 00
2024-05-18 14:14:46.672 T 30: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorFastPlus(0xE4), data: 00 00 00 00 EE 00 00 (offset 35)
2024-05-18 14:14:46.861 T 31: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorSlowPlus2(0xE3), data: 04 00 00 00 00 00 00 00 00 00 00 01 0E 00 64 46 00 00 00 00
2024-05-18 14:14:47.066 T 32: [emsesp] boiler(0x08) -B-> All(0x00), UBAMonitorWWPlus(0xE9), data: 05 80 00 80 00 00 00 00 00 46 3C 00 00 02 00 00 00 00 00 00 00 00 00 05 02 00
2024-05-18 14:14:47.369 T 34: [emsesp] boiler(0x08) -W-> Me(0x0B), UBAParametersPlus(0xE6), data: 01 46 00 4B 64 0A 00 00 06 FA 05 01 02 64 0A 03 00 00 00 1E 01 00 00 00 01 00 00
2024-05-18 14:14:47.633 T 37: [emsesp] Me(0x0B) -R-> boiler(0x08), UBAParameterWWPlus(0xEA), length: 27
2024-05-18 14:14:47.792 T 39: [emsesp] Me(0x0B) -R-> boiler(0x08), UBAParameterWWPlus(0xEA), length: 27 (offset 27)
2024-05-18 14:14:47.906 T 41: [emsesp] Me(0x0B) -R-> boiler(0x08), WeatherComp(0x28), length: 27
2024-05-18 14:14:47.936 T 42: [emsesp] boiler(0x08) -W-> Me(0x0B), WeatherComp(0x28), data: FF 32 23 1E 00 05
from ems-esp32.
Side note: since applying the beta firmware, i've been seeing this. Just keeps spinning:
from ems-esp32.
Side note: since applying the beta firmware, i've been seeing this. Just keeps spinning:
refresh browser cache help?
from ems-esp32.
Yes might have needed it. Seems ok now.
from ems-esp32.
Thanks, I had seen Tom's video actually. I'm not sure if that method will ensure my boiler's weather compensation add-on kit will continue to work, it may do. Anyway, I decided to stick with using my EMS-Bus gateway with Home Assistant automations because it lets me run two weather curves - one low, one high. The boiler's primary heating curve is set really low: 35 to 45 deg. Then when needed, either for hot water demand or to warm up a room that's too cold, the curve is temporarily boosted to 60 to 75 deg. Gives a nice combo of very efficient flow temps 95% of the time then very rapid warm up if a room was unoccupied and the heating was off. E.g. my bedroom is off all day in winter but it will warm up as much as 5 degrees in only an hour, just before bed time.
from ems-esp32.
Related Issues (20)
- correct firmware naming HOT 7
- Long raw custom entities is crashing gateway HOT 10
- RTC WAtchdog reboots and strange system/send with NAN HOT 29
- BC400 - ems-esp/boiler_data/hpactivity is removed 3.7.0-dev.30 [BC400] HOT 8
- Error A11 816 after updating to 3.7.0 dev HOT 14
- nrgtotal, nrgheat, dhw.nrg are not reported correctly in 3.7.0-dev.30 compared to 3.6.5 HOT 3
- BC400: Cooling Energy and Consumption values without digit after comma HOT 4
- Devices tab - count of entities in different column HOT 3
- HA MQTT: climate entity id's are language dependend HOT 8
- API: Post/Put does not change http Get values immediately for thermostat/dhw entities - just on next telegram read HOT 7
- [3.7.0-dev.32] virtual remote w/ RC220 HOT 5
- Heatpump with BC400/RC220 DHW mode and Energiemanager HOT 4
- Feature: Dashboard showing all data (favourites, sensors, custom) HOT 1
- Can't upgrade from 3.6.4 to 3.6.5 HOT 5
- Heatpump WLW186 with BC400/RC220 and failure message HOT 3
- Low memory error HOT 13
- module doesnt restart HOT 6
- Regression: "exit" command does not work in standalone builds any more HOT 8
- Sporadic restarts since dev.33 HOT 10
- many MQTT failures after update to dev-29+ HOT 31
Recommend Projects
-
React
A declarative, efficient, and flexible JavaScript library for building user interfaces.
-
Vue.js
🖖 Vue.js is a progressive, incrementally-adoptable JavaScript framework for building UI on the web.
-
Typescript
TypeScript is a superset of JavaScript that compiles to clean JavaScript output.
-
TensorFlow
An Open Source Machine Learning Framework for Everyone
-
Django
The Web framework for perfectionists with deadlines.
-
Laravel
A PHP framework for web artisans
-
D3
Bring data to life with SVG, Canvas and HTML. 📊📈🎉
-
Recommend Topics
-
javascript
JavaScript (JS) is a lightweight interpreted programming language with first-class functions.
-
web
Some thing interesting about web. New door for the world.
-
server
A server is a program made to process requests and deliver data to clients.
-
Machine learning
Machine learning is a way of modeling and interpreting data that allows a piece of software to respond intelligently.
-
Visualization
Some thing interesting about visualization, use data art
-
Game
Some thing interesting about game, make everyone happy.
Recommend Org
-
Facebook
We are working to build community through open source technology. NB: members must have two-factor auth.
-
Microsoft
Open source projects and samples from Microsoft.
-
Google
Google ❤️ Open Source for everyone.
-
Alibaba
Alibaba Open Source for everyone
-
D3
Data-Driven Documents codes.
-
Tencent
China tencent open source team.
from ems-esp32.